Air Circuit Breaker
BW-2000
Rated Current from 630 to 2000A
Features
- Mounting type: Draw out type
- Operation mode: Electric and manual operation
- Number of poles: 3 and 4
- Tripping categories: Intelligent controller, under-voltage instantaneous (or delay) release, and shunt release
- Intelligent controller can be divided into two types based on functions: XSIC-A and XSIC-P
- Under-voltage release has instantaneous and delay types.
Specification
- Standard: IEC60947-2
- Draw out type
- Rated Current: 630, 800, 1000, 1250, 1600, 2000A
- Pole: 3P / 4P
- Frequency: 50 / 60Hz
- Rated Voltage Ue: 690V
Breaking Capacity
Model | HS | HN | |
Icu / Ics (kA) | 690V | 50 / 50 | 55 / 55 |
500V | 50 / 50 | 80 / 80 | |
380/400/415V | 80 / 50 | 85 / 85 | |
240V | 80 / 50 | 85 / 85 | |
Icw (kA) 1 sec | 415V | 50 | 65 |
690V | 50 | 65 |
Protection
- Overload Long time delay Protection
- Short-circuit Short time delay Protection
- Short-circuit Instantaneous Protection
- Unsymmetrical Ground Fault / Earth Leakage Protection
- Load Monitoring Protection (Only for XSIC-P controller)
- Phase Failure Protection