Molded Case Circuit Breaker
BM160-HB
Rated current: 125, 140, 160A
Specification
- Thermal magnetic
- Standard: IEC60947-2
- Rated current: 125, 140, 160A
- Pole: 3P, 4P
Breaking Capacity
Model |
3P |
4P |
|
Icu (kA) |
500V |
25 |
|
440V |
42 |
||
380V |
50 |
||
220V (240V) |
85 |
Ics = 50%Icu
Protection
- Overload portection
- Short circuit pretection
- Certification
- Related Products
-
- Files Download
-
-
Characteristic Curve for BM100-HBN & BM160-HB/HC/HS & BM250-HB/HC/HS (PDF)
Characteristic Curve (PDF)